Content:
Environment One's standard Generator Gas Analyzer (GGA) can also be supplied in a portable configuration. The PGA incorporates the same hydrogen gas sensor/analyzer and system electronics found in our other hydrogen gas purity systems. The PGA is specifically intended for use in non-hazardous environments and/or as an emergency back-up in the event a power plant's primary purity monitoring system is compromised.
Portable Gas Analyzer Specifications
| MEASUREMENT CHARACTERISTICS | | Case Purity | 70 to 100% H2 in air | | Purge | 0 to 100% H2 in CO2 0 to 100% Air in CO2 | | Hydrogen Flow Rate | 100 to 700 cc/min | | Resolution | +/- 0.1% | | Accuracy | +/- 0.5% F.S. on H2 in Air | | | +/- 1.0% F.S. on H2 or Air in CO2 | | Linearity | +/- 1.0% F.S. | | Drift | <0.2% / month | | | | ELECTRICAL CHARACTERISTICS | | Power | 115 VAC, 50/60 Hz or 230 VAC | | Output, Signal | 4-20 mA | | | | MECHANICAL CHARACTERISTICS | | Enclosure Dimensions | 8.5" x 10" x 11" | | Area Classification | None | | Hydrogen Pressure | 100 psi maximum | | Gas Connections | 1/4-inch female NPT |
|