Advancements in air-cooled generator designs have resulted in increasingly higher power ratings. The higher power densities place significantly greater stresses on materials and structures, making slight decreases in cooling efficiencies much more critical. Probability of overheating in these air-cooled machines becomes greater as designs are pushed closer to their critical limits.

The GCM-A2 warns of an impending failure much faster than RTD’s or thermocouples. Why? Because RTD’s and thermocouples need to be physically near the hotspot, or wait until overheating progresses to the point that the temperature near the RTD or thermocouple rises sufficiently for the sensor to detect it. This results in a significantly larger “fault,” possibly a catastrophic one. The GCM-A2, on the other hand, detects the pyrolysis particles emitted into the cooling air as a result of overheating or arcing virtually anywhere in the machine.

How the GCM-A 2 Works

 
The GCM-A2 monitors two air sample lines using a submicrometer particle detector. One line monitors ambient air, which serves as a reference. The other line is used to monitor generator cooling air, which is then compared against the particle level of the reference. High particle levels in the generator cooling air, without a corresponding increase in the ambient air, confirms the source of the pyrolysis particles is from within the generator.

In the event overheating occurs, large numbers of pyrolysis products are created in the generator cooling air. When the signal level corresponding to the difference between the generator cooling air and ambient air exceeds a predetermined (adjustable) set point, the result is a differential alarm, causing the alarm contacts to close. Individual contacts will also close if the outputs corresponding to the ambient air and/or generator cooling air exceed predetermined (adjustable) set points.

GCM-A 2 Specifications

MEASUREMENT CHARACTERISTICS
Detection PrincipleSubmicron particle detector
Air Flow RateAdjusted by Zone Manifold, nominal 14 LPM
Readout (LED bar graph) 
    Ambient Air0 to 100% scale
    Generator Air0 to 100% scale
 
ELECTRICAL CHARACTERISTICS
Power Input115 VAC, 50/60 Hz (230 VAC, 50/60 Hz optional)
Output Relays 
    Ambient Alarm, Zone 13 A @ 120/240 VAC
3 A @ 30 VDC
100 mA @ 125 VDC
    Generator Alarm, Zone 2
    Differential Alarm
    Warning
    System Trouble
    Flow Trouble
4-20 mA outputs500 ohms max
    Ambient Air4-20 mA = 0-100%
    Generator Air4-20 mA = 0-100%
    Differential4-20 mA = 0-100%
 
MECHANICAL CHARACTERISTICS
Dimensions, overall24" h x 24" w x 11.75" d
 (610 mm x 610 mm x 299 mm)
Weight, approximate85 lbs (38.6 kg)
Connectors, gas inlet3/8" NPT, standard
Ambient temperature32-122 F (0-50 C)
Area ClassificationNon-Hazardous
Relative Humidity0-95%
Controls5-key switch keypad with LED indicators and liquid crystal display